DN80 Fuel Shut-off Valve

DN80 Fuel Shut-off Valve

VIC083.25M
Last items in stock
Tax included

Fuel Shut-off Valve DN80 P.max 1Bar standard 98°C

 

The VIC083 safety valves. with positive action, not activated by external energy, built for the purpose of intercepting the flow of fuel to the burner to prevent the temperature of the water in the system delivery circuit from reaching the boiling point.

The valve closes due to:

Puncture or cut the capillary and/or sensor bulb. ATTENTION: As they are positive action valves, in this case it is no longer possible to reset the valve.

Raising the water temperature until it reaches the calibration point. In this case it is possible to reset the valve only if the temperature drops by at least 10 °C with respect to the calibration value indicated on the label.

NOTE:

The original copy of the calibration report is supplied with each valve. In addition to the technical data of the valve, this document also contains the serial number which is also shown on the seal fixed to the valve body. The document is stamped and validated by the INAIL technician who assisted in the calibration.

It is advisable to keep it with extreme care as in case of loss it is not possible to issue duplicates.

In compliance with:

PED Directive 2014/68/EU

Marking and Normative References
Compliant with Directive PED 2014/68 / UE (ex 97/23 / CE) Approved and calibrated INAIL Approved according to "RACCOLTA R" ed. 2009 - Application technical specifications of Title II of Ministerial Decree 1.12.75
Fluids
gas of the 3 families, diesel and fuel oil
Max pressure
1Bar
Attack
Flanged
Standard calibration temperature
98 ° C
Cockpit connection
M1 / 2 "
Standard capillary length
5mt
Inches DN
3 - DN 80