The control unit was designed and built according to European Regulations to verify the presence of gas in a versatile way thanks to the possibility of connecting up to 8 conventional sensors. The control unit has both pre-alarm relays and general alarm relays.
The control unit has two levels of danger, which are:
LEVEL I, pre-alarm. This data is variable, it is possible to modify the intervention of the pre-alarm, probe by probe, based on the type of system to be controlled, the level can be selected from 3% to 16% of the LEL or from 45 to 240 ppm
LEVEL II, general alarm. It is set at 20% of the LEL or 300 ppm LEVEL II, general alarm. It is set at 20% of the LEL or 300ppm
Thanks to the most innovative technologies, this gas detection control unit is suitable for installation in industrial environments and underground car parks, applying the "DM 01/AC02/1986.
Technical features:
· Primary power supply BX308xp version: 15 Vdc
· Secondary power supply from battery Max 2.2 Ah: 12.7 V. dc
· Max Battery Charge 2.2 Ah: checked
· Absorption: 18 W in Alarm
· Conventional Probes: Max 8 Catalytic, Electrochemical, Semiconductor, Pellistor
· Explosive alarm threshold: 20% of LEL and 300ppm
· Input signal: 4 ÷ 20 mA at 150 Ohm
· Accuracy: 1 % FS
· Display: 4 rows 20 columns
· Positive Security: Selectable
· Pre-alarm output relay: ON – OFF
· Alarm output relay: Switching
· Failure relay: ON – OFF
· Manual alarm signal: incorporated
· Working temperature: -10°C ÷ + 60°C
- Marking and Normative References
- UNI EN 50194-1
- Operating temperature
- from -10 ° C to + 60 ° C
- Alarm signaling
- Optics (LED) and acoustics (Buzzer)
- Degree of protection
- IP65
- Power supported
- 230vac 50 / 60Hz
- Exit
- analog 4-20mA
- Gas alarm threshold
- adjustable
- Detection areas
- 8